By Alex Christou. 19 sources listed at the end.

On this page

MVHR (mechanical ventilation with heat recovery) is a fan-driven system that pulls stale air out of kitchens and bathrooms, brings filtered fresh air into living rooms and bedrooms, and passes the heat across on the way. It works well in airtight homes. It also fails quietly: the Innovate UK building performance study, published in 2016, found "only 16% of systems being found to have been commissioned correctly".

Quick answer: MVHR is whole-home ventilation that recovers heat from outgoing air. It suits airtight new builds and deep retrofits. The Centre for Sustainable Energy (CSE) says systems start from around £3,000 and can cost well over £10,000. It does not heat or cool a house, and it only performs if it is designed, commissioned and filtered properly.

Last checked 26 October 2026: Building Regulations, the Ofgem price cap, the CSE page and UK field studies. Not checked: any Brighton MVHR price (we found none), manufacturer list prices (not published), Energy Saving Trust pages (blocked to us).

What is MVHR? The 30-second answer

MVHR takes air out of the kitchen and wet rooms, takes air in from outside, and lets the two streams swap heat inside a heat exchanger without mixing. The house loses less heat than it would through an open window or a plain extract fan.

What the letters mean

"Heat recovery ventilation" and "HRV" describe the same idea. "MVHR system" means the whole installation: unit, ducts, room valves and filters.

What is in the system

  • One central unit with two fans, a heat exchanger and filters, usually in a loft, cupboard or utility room.
  • Ducting from the unit to every room.
  • Extract valves in the kitchen and bathrooms, supply valves in the bedrooms and living rooms.
  • Two ducts to outside: fresh air in, stale air out.
  • A controller with at least background and boost settings.

Why UK homes have it

Tight houses leak less air, so they need ventilation that is planned instead of accidental. Approved Document F (2021 edition) says the efficiency of MVHR systems should improve as the dwelling becomes more airtight. Part F lists both MVHR and continuous extract as suitable for all dwellings, so it does not force MVHR on new builds. Be wary of any installer page that says the regulations strongly favour MVHR; we found no such wording in Part F.

How does an MVHR system work?

Step by step

  1. Extract. A fan draws stale, humid air from the kitchen and bathrooms through ducts to the unit.
  2. Filter. Air passes through filters before it reaches the exchanger. Zehnder's data sheet for its ComfoAir Q350 lists G4, M5 and F7 filter options.
  3. Pass heat across. In the exchanger the warm outgoing air heats the cold incoming air through thin plates. The two streams stay separate.
  4. Supply. A second fan sends the warmed, filtered air to bedrooms and living rooms. The stale air leaves through its own duct.

Background and boost modes

Part F treats MVHR as continuous ventilation. The unit runs at a low background rate all day and steps up on boost, for cooking or showering. Part F gives a minimum whole-dwelling rate of at least 0.3 litres per second (l/s) per m2 of internal floor area. It also sets floors of 19, 25, 31, 37 and 43 l/s for one to five bedrooms (Table 1.3, 2021 edition). A three-bedroom home therefore needs at least 31 l/s.

Summer bypass

Part L requires a summer bypass: a way to skip the heat exchanger or reduce its heat recovery. On a warm day the unit can then bring in outdoor air without warming it.

How much heat does MVHR really recover?

The exchanger can reach about 90%. The whole system delivers less. The figures in circulation measure different things, so keep them apart.

Figure What it measures Source and date
Up to 95% Marketing claim for the heat exchange block Nuaire MRXBOX95-WH1-AE datasheet, undated, read 26 Oct 2026
96% Marketing claim for the unit Zehnder ComfoAir Q350 UK data sheet, undated, read 26 Oct 2026
85% to 91% SAP test efficiency, falling as the unit serves more wet rooms Nuaire datasheet, SAP Appendix Q table, read 26 Oct 2026
86% to 91% Passive House certified heat recovery rate (enthalpy and standard exchanger) Zehnder ComfoAir Q350 UK data sheet, read 26 Oct 2026
80% to 90% General range CSE, reviewed July 2026
73% Minimum allowed Approved Document L Vol 1, 2021 edition incl. 2023 amendments, para 6.56
About 75% SAP prediction after a 15% in-use factor for insulated ductwork NHBC Foundation NF 52, August 2013
Below 70% Measured in one Slough home when loft air fell under 10°C NHBC Foundation NF 52, August 2013

Why the field number is lower

The 2013 NHBC Foundation report, written by BRE, studied ten Code Level 6 homes at Greenwatt Way in Slough. In one of them, with the unit in the loft, the report found that as loft air fell below 10°C, the "thermal efficiency of the system fell below 70%". The laboratory had measured the unit at around 90%. The report puts the gap down to heat lost through the unit casing and the ductwork. It also notes that SAP, the government's home energy model, takes 15% off laboratory results for systems with insulated ductwork, which gave a predicted figure of about 75%.

What to take from it

Treat 90% as the best case for the exchanger alone. Ask for the SAP or certified figure, not the brochure figure, and ask where the unit and ducts will sit. A unit in a cold loft with long runs loses more than one inside the heated space. The NF 52 findings are from 2013, so read them as a warning about installation quality, not a measurement of every current unit.

Do you still need trickle vents with MVHR?

No. Approved Document F, 2021 edition, para 1.72, says "background ventilators should not be installed with mechanical ventilation with heat recovery". The reason it gives is to avoid unintended air pathways. A trickle vent lets air bypass the heat exchanger, so the house loses heat the system was meant to recover.

The same document, para 3.11(c), says existing background ventilators should be covered or sealed shut when the dwelling is ventilated by MVHR. A common claim is that MVHR means no trickle vents. Verdict: true, and Part F puts it more firmly than most installers do.

Adding MVHR to an older home

Sealing existing vents only helps if the house is airtight enough for the system to work. Part F para 3.15 notes that replacing windows is likely to increase airtightness, and that where MVHR is not fitted, ventilation must be no worse than before. Ask for an air leakage test before you decide, because in a leaky house much of the heat escapes through gaps the unit never sees.

Does MVHR cool the house? Summer bypass and air conditioning

No. Nicholas Vaisey of CVC Direct, a ventilation supplier, put it plainly in Passive House Plus on 20 March 2020: "An MVHR system on its own does not provide cooling or heating." He added that the cooling effect of the summer bypass is limited and often not enough to counteract the heat gains. He is a supplier speaking in trade press, so read it as informed opinion, not a test result.

What the bypass does and does not do

The bypass stops the exchanger from warming incoming air. It cannot take heat out of a room. On a cool summer night that gives some relief; on a hot afternoon it brings in hot air.

MVHR and air conditioning do two different jobs

MVHR moves air in and out. Air conditioning removes heat. Combined projects exist: Sub-Cool FM, a firm in our directory, has a project page for a West Sussex timber-frame new build with MVHR through the whole house plus ducted Mitsubishi Electric air conditioning in six rooms. The page gives one total for both systems, so we do not quote it as an MVHR price. The cooling there comes from the air conditioning.

See our guide to MVHR with air conditioning for how the two systems sit together.

If overheating is the real problem

If you are comparing cooling options, our guides on the best air conditioning for a home, air conditioning for a bedroom and air conditioning in flats cover the choices. A reversible unit may also act as an air-to-air heat pump; see air conditioning vs heat pump. To size a unit, the BTU calculator gives a starting figure in kW and BTU.

MVHR vs MEV, dMEV, PIV and extract fans

The table has no cost column because we found no like-for-like prices.

System What it does Heat recovery Suits Main limit
MVHR Supplies and extracts air through ducts, passing heat across Yes Airtight new builds and deep retrofits Ducting space, commissioning, filter upkeep
MEV (continuous mechanical extract) Extracts from wet rooms continuously; fresh air comes in through vents No Homes where background vents are acceptable Heat leaves with the extracted air
dMEV (decentralised extract) Individual continuous extract fans in each wet room No Simpler layouts and retrofits As MEV
PIV (positive input ventilation) Pushes filtered loft or outdoor air into the home No Draughty or damp homes with no airtightness plan Does not recover heat
Extract fan Removes air from one room on demand No Occasional moisture control Not whole-home ventilation

PIV and MEV in brief

Our MVHR vs PIV guide covers that choice in more detail, and positive input ventilation has its own page.

Single-room and decentralised units

Part F notes that continuous extract comes in decentralised form, and para 3.26 covers a single-room heat recovery ventilator in a wet room added to an existing home. CSE puts decentralised MVHR at from £600 per fan. That figure is per fan and does not cover a whole house. Ask for the number of units, what each serves and whether commissioning is included.

Who MVHR suits and who should skip it

Good fit

  • A new build or deep retrofit with air permeability low enough that the house cannot ventilate itself. Part F treats a design air permeability above 5, or an as-built result above 3 m3/(h.m2) at 50 Pa, as "less airtight". Below that, its natural ventilation route no longer applies, leaving continuous extract or MVHR.
  • A home with space for the unit and ducts in the design stage.
  • Occupants who will leave it running and change filters.

Poor fit

  • A leaky Victorian terrace where draught-proofing and working extract fans have not been sorted. Fabric and basic ventilation come first.
  • A home with no practical route for ducts.
  • Anyone who plans to switch the unit off to save electricity. The Innovate UK study found half of the sampled projects had occupants who disabled the system, most often out of concern for running cost.

Retrofit realism

CSE says it can be "difficult to retrofit MVHR because of the space needed" for ducting and the unit. It is one reason to look at decentralised units or a different system. We found no Brighton-specific rule on MVHR in conservation areas or listed buildings, so ask the council before you plan external grilles.

Is MVHR worth it? What UK field studies found

Yes in an airtight home, if it is designed, commissioned, filtered and left on. The evidence says many are not.

What the BPE meta-study measured

The Innovate UK Building Performance Evaluation meta-study, published in 2016, looked at 85 dwellings across 29 projects. Its findings:

  • Only 16% of systems were commissioned correctly for airflow and balancing.
  • 56% of installations met the design airflow.
  • 52% had a supply and extract imbalance above 15%.
  • 88% of rigid-duct systems met design airflow, against 40 to 44% of flexible-duct systems.
  • Half of the projects had occupants who disabled the system.

The executive summary also says that "well designed, installed, maintained and used" systems can make useful contributions to energy reduction and good ventilation.

What it did and did not show

Energy use was lower in MVHR homes, but 77% of the MVHR dwellings with energy data were Passivhaus builds, so the saving cannot be pinned on MVHR alone. Average and peak carbon dioxide levels were lower in MVHR homes. The effect on relative humidity was "not clear".

A paper by Gupta and colleagues looked at 54 low energy dwellings from the same 29 projects. It found the rationale for MVHR "borne out", but also a prevalence of sub-optimal systems. A 2016 retrofit case study in Energy and Buildings (White and colleagues) found an installed system underperformed predictions because of control unit and ductwork faults, then improved after remedial work. We read only the abstract of that paper.

What this means for you

The studies are from 2013 and 2016. We found no newer UK sample of this kind, so treat the numbers as risks to ask about, not a verdict on every installation today.

Claim test: does it make mould disappear?

No. The 2016 study found the effect on relative humidity not clear. CSE says filters help keep pollen and other particles out. They do nothing about moisture or pollutants made indoors, and a switched-off or unbalanced unit does not ventilate properly. Mould needs moisture and cold surfaces. MVHR can reduce moisture if it works, but we found no source showing it eliminates mould.

What does MVHR cost to buy and run?

Installed cost

CSE says MVHR systems "start from around £3,000 but could cost well over £10,000". Other figures we found are leads, not benchmarks, because the scope of each is different.

Figure Scope Source and date
From £3,000 to well over £10,000 MVHR systems CSE, reviewed July 2026
From £600 per fan Decentralised units, scope varies CSE, reviewed July 2026
£3,000 to £7,000 Complete installation, varies with property size MyBuilder price guide, updated August 2026
£4,000 to £7,000 Typical 3-bed house, supply and fit Trade2Base pricing blog for installers, June 2026
£8,000 to £20,000 Retrofit into an existing home Deeside.com article, September 2025

You may read that a whole-house DIY system costs under £2,500. We found no primary source for that. The independent ranges start at £3,000, and a retrofit that includes ducting, commissioning and the Part F notice sits well above it. Our full MVHR cost guide covers what changes the price. For the wider picture, see our air conditioning cost guide.

Running cost worked example

This is our calculation, not a quoted source. The inputs are 31 l/s (the Part F minimum for a three-bedroom home), running 8,760 hours a year at that constant rate, and electricity at 26.32p per kWh. The rate is the Ofgem price cap for 1 October to 31 December 2026, with no VAT on electricity from 1 October 2026 to 31 March 2027. Ofgem announces the January cap on 25 November 2026, so re-check it.

Specific fan power Source of figure Power Per year Cost
0.42 W/(l/s) Nuaire SAP table, kitchen plus 1 wet room 13.0 W About 114 kWh About £30
0.90 W/(l/s) Nuaire SAP table, kitchen plus 5 wet rooms 27.9 W About 244 kWh About £64

These exclude boost use, filter replacement and the standing charge. Real homes can run above the minimum airflow, so treat the figures as a floor. Specific fan power is the electricity the fans use per litre of air moved. Part L caps it at 1.5 W/(l/s) for continuous supply and extract in the 2021 edition.

Filters and servicing

MyBuilder, a trades marketplace, puts annual servicing at £100 to £300 and filter replacement at £80 to £150. We found no independent figure. Ask any installer what a filter set for your unit costs and how often it changes.

Noise, filters and day-to-day use

Switching the unit off removes the ventilation the house was designed around. If running cost is the worry, check the worked example above against your own system.

Noise

Part F's guideline is 30 dB LAeq,T in bedrooms and living rooms at the minimum low rate, and 45 dB in kitchens and bathrooms at the high rate. There is no requirement to test noise. In the NF 52 study, 53% (23 of 43) of measured rooms failed the CIBSE noise limits before remediation, and 8% (3 of 38) after. Occupant complaints also included draughts from cool air dumping.

Filters

Filters need changing. Part F 2026 says access to filters should not need tools or removal of the main front cover. That edition is not yet in force. Ask whether the unit you are quoted for has tool-free filter access anyway.

What Part F and Part L require in England

Part F and Part L are general information for England. Check with building control or a solicitor for your own case.

Requirement Rule Edition and paragraph
Minimum whole-dwelling rate At least 0.3 l/s per m2, with floors of 19, 25, 31, 37 and 43 l/s for 1 to 5 bedrooms ADF 2021, para 1.24, Table 1.3
Trickle vents Not to be installed with MVHR; existing ones sealed ADF 2021, paras 1.72 and 3.11(c)
Commissioning Systems must be commissioned and a notice given to building control ADF 2021, paras 4.1 to 4.2
Airflow measurement Required in new dwellings ADF 2021, para 4.2
Measuring device Accurate to 5%, with UKAS-accredited calibration within 12 months ADF 2021, para 4.10
Heat recovery A minimum efficiency of 73% ADL Vol 1, 2021 incl. 2023, para 6.56
Summer bypass Required ADL Vol 1, 2021 incl. 2023, paras 6.55 to 6.56
Fan power 1.5 W/(l.s) for continuous supply and extract ADL Vol 1, 2021 incl. 2023, paras 6.55 to 6.56

The 2026 editions

Approved Document F 2021 remains the current guidance. A 2026 edition takes effect on 24 March 2027 for building work that is not higher-risk. It adds a rule that supply and extract balance should be within 10% in background mode (para 4.21), and it limits flexible duct to 200 mm in length, for final connections only (para 1.79). Approved Document L 2026 Table 5.6 sets fan power at 1.4 W/(l.s) for new dwellings and 1.5 for existing ones, with the same 73% minimum. The maximum air permeability for a new dwelling is 8.0 m3/(h.m2) at 50 Pa in both editions. The 2026 Approved Document L refers to the Future Homes Standard 2026, and we have not read what it requires for ventilation beyond Parts F and L.

Questions to ask an MVHR installer

  1. Ask for the Part F commissioning notice and the airflow readings, room by room, for your home.
  2. Ask whether the airflow device used is calibrated to the standard in Part F para 4.10, and when.
  3. Ask whether the ducts are rigid or flexible. The BPE meta-study found 88% of rigid-duct systems met design airflow, against 40 to 44% of flexible systems.
  4. Ask where the unit and ducts will sit, and whether they are inside the heated space.
  5. Ask for the certified SAP efficiency and specific fan power of the exact model, not the brochure maximum.
  6. Ask what the stated airflow will be in background mode and what noise level that gives in bedrooms.
  7. Ask how filters are accessed, what a replacement set costs and who does the change.
  8. Ask for three itemised quotes for the same specification, including commissioning, and compare them.

MVHR installers serving Brighton and Hove

Our installer pages show each firm's F-gas register status. See MVHR installers serving Brighton and Hove for the full write-ups, and all installers in Brighton and Hove for the wider list.

That list has 11 firms whose own sites say they fit MVHR, heat recovery ventilation or PIV. Five are summarised below. Venue data was checked on 10 October 2026 and the firms' pages were read on 26 October 2026. What each firm says about itself is a claim, not evidence.

Firm Base F-gas register What its page lists
Cool Temp Air Conditioning and Ventilation Hove Technology Centre, Hove REF1021563, found on the register MVHR and heat recovery, system balancing, testing and commissioning
Ernest Air Cooling Shoreham-by-Sea REF1013304 Dedicated MVHR page; new build, retrofit, commissioning, servicing
Cen Air Solutions Worthing Listed on the Quidos F-Gas register MVHR and PIV ventilation systems
Sub-Cool FM Rowfant, near Crawley REF1013926 MVHR project page with air conditioning
4Facilities Eastbourne REF1018371 MVHR under commercial systems

Only Cool Temp is based in Brighton and Hove. The others serve the area from elsewhere in Sussex. 4Facilities is led by commercial work, and its page says MVHR serves a different purpose from air conditioning and that it assesses whether ventilation, cooling or a combined approach suits a building. Cool Temp's company was incorporated on 22 April 2024, so the firm is new, though individuals there may have earlier experience. Cen Air's company was incorporated on 5 April 2019.

We did not verify MVHR-specific training, commissioning equipment or airflow-test competence for any firm. "Not found on the register" does not mean "not certified". We list firms. We do not recommend any. We found no price for MVHR in Brighton on any page.

Questions

What is mechanical ventilation in a building?
Mechanical ventilation in a building uses fans to move air instead of relying on open windows and vents. Approved Document F, 2021 edition, covers it in England and requires commissioning for mechanical systems. MVHR is one type; it adds a heat exchanger. Extract-only systems are another and do not recover heat.
How much does it cost to install a heat recovery ventilation system in the UK?
The cost to install heat recovery ventilation in the UK starts from around £3,000 and can pass £10,000, according to CSE in July 2026. Decentralised units start from £600 per fan. Other estimates we found, such as £3,000 to £7,000 from MyBuilder, cover different scopes, so compare itemised quotes for the same specification.
Should I turn on MVHR all day?
Yes, MVHR should run all day. Approved Document F treats it as continuous ventilation at a low background rate with boost on top. The BPE meta-study found half of sampled projects had occupants who disabled the system, mostly over running cost. On our worked example the fans use about £30 to £64 a year at minimum airflow, excluding boost.
Does a heat recovery system use a lot of electricity?
A heat recovery system uses little electricity at minimum airflow. Our calculation, using Nuaire's SAP fan power figures and the 26.32p per kWh Ofgem cap, gives about 114 to 244 kWh a year. That is about £30 to £64. It excludes boost use and higher airflow rates, so a real home can use more.
Does MVHR stop mould?
MVHR does not stop mould on its own. The BPE meta-study found its effect on relative humidity "not clear". Carbon dioxide was lower when systems worked. Mould needs moisture and cold surfaces, so airtightness, heating and extract in wet rooms matter too. We found no source showing MVHR eliminates mould.
What is the best air ventilation system for a home in the UK?
There is no single best system. Part F permits MVHR in every dwelling and other systems in many. MVHR suits airtight new builds and deep retrofits; a leaky older home may be better served by extract or PIV. CSE says retrofit MVHR can be difficult because of space for ducting. Get a ventilation assessment before choosing.

Sources

  1. Ventilation: Approved Document F, GOV.UK (read 26 Oct 2026)
  2. Approved Document F (2026), GOV.UK (read 26 Oct 2026)
  3. Approved Document F Volume 1, 2021 edition, PDF (read 26 Oct 2026)
  4. Approved Document F Volume 1, 2026 edition, PDF (read 26 Oct 2026)
  5. Approved Document L Volume 1, 2021 edition incorporating 2023 amendments, PDF (read 26 Oct 2026)
  6. Approved Document L (2026), GOV.UK (read 26 Oct 2026)
  7. Approved Document L Volume 1, 2026 edition, PDF (read 26 Oct 2026)
  8. Innovate UK BPE, Characteristics and performance of MVHR systems, meta-study, 2016 (read 26 Oct 2026)
  9. Gupta and others, Characterising the actual performance of domestic MVHR systems, Oxford Brookes RADAR (read 26 Oct 2026)
  10. NHBC Foundation NF 52, Assessment of MVHR systems and air quality in zero carbon homes, August 2013 (read 26 Oct 2026)
  11. White and others, Performance evaluation of an MVHR system as part of UK residential energy retrofit measures, Energy and Buildings 110, 2016, abstract only (read 26 Oct 2026)
  12. Centre for Sustainable Energy, Mechanical ventilation with heat recovery, reviewed July 2026 (read 26 Oct 2026)
  13. Ofgem, Changes to energy price cap between 1 October and 31 December 2026 (read 26 Oct 2026)
  14. Nuaire MRXBOX95-WH1-AE datasheet (read 26 Oct 2026)
  15. Zehnder ComfoAir Q350 UK data sheet (read 26 Oct 2026)
  16. MyBuilder, How much does an MVHR system cost?, updated 21 August 2026 (read 26 Oct 2026)
  17. Trade2Base, MVHR installation costs UK, 14 June 2026 (read 26 Oct 2026)
  18. Deeside.com, Understanding MVHR costs in 2025, 25 September 2025 (read 26 Oct 2026)
  19. Passive House Plus, Don't see MVHR as a heating or cooling system, CVC Direct, 20 March 2020 (read 26 Oct 2026)

Written and checked by Alex Christou. Found a mistake? Tell us; our corrections policy explains what happens next.